Understanding Mil-Std 1399 Section 300 Part 1

MIL-STD-1399 Section 300 Part 1 — Summary and Acceptance Criteria

Established in 2018, MIL-STD-1399-300-1 establishes mandatory AC electrical interface requirements to ensure compatibility between user equipment and shipboard AC power systems. It defines the power characteristics, tolerances, and required compliance tests for equipment connected to Navy AC power systems.

The standard covers three system types:

  • Type I: 115/440 Vrms, 60 Hz (primary ship service distribution)
  • Type II: 115/440 Vrms, 400 Hz, ungrounded
  • Type III: 115/440 Vrms, 400 Hz, ungrounded, with tighter tolerances

It includes mandatory grounding, current waveform limits, surges, spikes, pulsed load behavior, and numerous susceptibility tests (voltage/frequency tolerance, spike, emergency conditions, AGD, insulation, etc.). Table I lists all required compliance tests.

This article provides an overview of the standard and makes references to sections and figures that are found within the document. You may download a copy of the standard  from the DLA quick-search site and download the standard from this page

If you are looking for MIL-STD-1399 compliant power supply, ETA-USA offers Type I, 60Hz compliant models available in 500~2400W on its Military and Aviation page. 


POWER SYSTEM TYPES AND CHARACTERISTICS

Type I — 60 Hz Power (Primary Shipboard AC Power)

Definition: 115 or 440 Vrms, 60 Hz; ungrounded or high-resistance grounded (440 V) or solid-grounded (115 V).

Applications: Standard ship service and lighting loads.

Type I System Characteristics (Table II Extracts)

  • Voltage tolerance: ±5% steady state (115 V or 440 V)
  • Frequency tolerance steady state: 60 Hz ± 2% (59–61.2 Hz)
  • Transient tolerances: defined envelopes (Figure 10) including excursions during faults and switching operations.
  • Harmonics:
    • THD ≤ 5%
    • Single harmonic ≤ 3%
    • Deviation factor ≤ 5% (3% for submarines)
  • Spike voltage: 900–1000 V peak (115 V systems) per Table V.
  • Emergency conditions:
    • Frequency excursion −100% to +12%
    • Voltage excursion −100% to +35%
    • Duration up to 2 minutes depending on case

Type II — 400 Hz Ungrounded

  • Limited-use system with wider tolerances than Type III.
  • Behavior of power decay is fast due to M/G set protective trip actions (interruptions occur within ms).

Type III — 400 Hz Ungrounded (Tighter Tolerances)

  • Used where precision 400 Hz is needed (avionics).
  • Tighter steady-state and transient tolerances than Type II.
  • Delivered typically as 115/200 V 400 Hz grounded-wye for aircraft servicing.

USER EQUIPMENT REQUIREMENTS (APPLICABLE TO ALL TYPES)

All equipment must comply with section 5.2. requirements, enforced through tests in Section 5.3.

Major required attributes:

Voltage & Frequency Compatibility

Equipment must tolerate all defined Type-specific envelopes (steady-state, transient, emergencies).

Current Harmonic Limits (Very Important for Power Supplies)

For 60 Hz equipment ≥1 kVA (your 1000 W AC/DC supply qualifies):

  • From 60 Hz–2 kHz: ≤3% of fundamental current
  • From 2 kHz–20 kHz: ≤(6000 / f)%
    (Figure 22)

For <1 kVA equipment: similar but slightly more lenient (Figure 23).

Power Factor Requirement

  • PF must meet criteria of 5.2.7.
  • Corrective action may be required for poor PF loads.

Inrush / Surge Current

The ratio of surge to rated current is limited by a curve (Figure 26).
Measured at specific AC zero-crossings.

Pulsed Load Requirements

Applicable to loads that switch or step power.

  • Must meet time-domain and frequency-domain limits.
  • TSD calculations must follow Appendix A.

Grounding and Leakage Current Limits

Includes:

  • Insulation resistance tests
  • Active ground detection (AGD) support
  • Simulated human-body ground-current tests (Figures 33–37)

Voltage Spike Survival

Equipment must survive spike tests:

  • 900–1000 V peak for 115 V systems
  • Sync angles: 0°, 90°, 180°, 270° on all conductors

REQUIRED COMPLIANCE TESTS

Table I lists all required tests by requirement category.
Major tests include:

  • Grounding test (5.3.1)
  • Power profile verification (phases, voltage, PF, current) (5.3.2)
  • Voltage & frequency tolerance test (5.3.3)
  • Transient tolerance test (5.3.4)
  • Voltage spike test (5.3.5)
  • Emergency conditions test (4 subtests: tr, ts, decay, excursion) (5.3.6)
  • Current waveform (harmonics) test (5.2.10 / 5.3.7)
  • Modulation susceptibility test (5.3.8)
  • Human-body leakage current tests (5.3.9)
  • Line-to-ground withstand & AGD tests (5.3.10)

115 VAC, 60 Hz, SINGLE-PHASE (TYPE I) IN DETAIL

The criteria for a single phase, 115Vac nominal AC/DC power supply described below outlines the acceptable criteria for a

Applicable System Characteristics (Table II for Type I)

For 115 Vrms 60 Hz Type I power, your supply must:

Voltage Characteristics

  • Nominal: 115 Vrms
  • Steady-state tolerance: ±5%
  • Transient tolerance envelope defined in Figure 10 (frequency & voltage).
  • Emergency voltage excursions: −100% to +35% for up to 2 minutes.

Frequency Characteristics

  • Nominal: 60 Hz
  • Steady-state tolerance: ±2% (58.8–61.2 Hz)
  • Transient: tight envelope defined in Figure 10.

Harmonics and Waveform

  • THD ≤ 5%
  • Individual harmonic ≤ 3%
  • Deviation factor ≤ 5%

Required Equipment Performance Requirements

Harmonic Current Limits (≥1 kVA Applies to Your 1000 W Converter)

Per 5.2.10 and Figure 22:

  • ≤3% of fundamental (60–2,000 Hz)
  • ≤6000/f % (2 kHz–20 kHz)

Inrush Current Limits

Must satisfy the surge/inrush envelope of Figure 26.

Voltage Spike Survival

Equipment must withstand:

  • 900–1000 V peak spikes on all conductors
  • At 0°, 90°, 180°, 270°

Emergency Condition Survival

Equipment must endure:

  1. tr limited-break interruption (~70 ms if unknown)
  2. ts emergency source transfer interruption
  3. Power decay behavior (loss of prime mover)
  4. Positive voltage excursion

Ground Detection Requirements

If installed on ships using AGD:

  • Must pass AGD susceptibility test (DC source applied through RAGD = 50 kΩ).
  • Single-phase AGD test circuit shown in Figure 39.

Insulation Resistance

Verified via megohmmeter per 5.3.10.1.


Acceptance Criteria Summary (What Your 115 V 60 Hz Power Supply Must Pass)

Your AC/DC power supply must pass all of the following to be MIL-STD-1399-300-1 compliant:

Electrical Compatibility

  • Operates over full voltage & frequency tolerance and transient envelopes
  • Survives all emergency condition subtests (tr, ts, decay, excursion)

Waveform Quality

  • Input current harmonics within Figure 22 limits
  • PF meets 5.2.7

Safety / Grounding

  • Leakage current within limits of 5.2.5 (human-body impedance tests)
  • AGD and L-G withstand tests passed

Transient Robustness

  • Survive specified voltage spikes (900–1000 V peak)

Operational Behavior

  • Inrush current within Figure 26 limits
  • Pulsed/ramped load limits if applicable
  • No excessive line-to-ground capacitance or current (5.2.4)

Additional Compliances 

In addition to the requirements outlined in 1399, the qualifying power supply must meet applicable sections of MIL-STD 461 (version dictated by the government procurement office, but the most current version is 461G). At the very least, expect conducted emissions CE101 & CE102; radiated emissions RE101 & RE102; conducted susceptibility  CS101, CS114, CS115. The supply may also need to perform with the limits of radiated susceptibility of RS101 and RS103. 


Mil-Std 1399 Power supplies For Purchase

ETA-USA offers military grade power supplies with customizable options that meet Mil-std 1399 Sec 300 Part 1 60Hz single phase requirement.  Contact an ETA-USA representative for price, lead-time, and CADS.  All ETA-USA power supplies ate TAA compliant and Mil-grade products are made in the USA.

Customizable AC/DC Mil-grade Power Supplies

CH-M500    DATASHEET

CH-M1000  DATASHEET

CH-M2000  DATASHEET

Mil-S-901 Compliant IP66 Rated AC/DC Power Supplies

LPM500  DATASHEET

LPM650  DATASHEET

LPM1100  DATASHEET

CUSTOMIZABLE ITE EXTERNAL DESKTOP POWER ADAPTERS

ITE Desktop Power Supply with Customizable to Fast Regulatory Approval

Powering a new product design can invites additional complexity for designers bringing a new product to market. Designing for safety, emissions, and regulatory standards alone can stop a project from obtaining that critical regulatory approval, piling on additional testing and engineering costs.  In addition, the final product will dictate the power demand, so it makes no sense for new product to be designed with a power converter in mind. 

Let ETA-USA’s external, desktop style power supplies deliver the DC voltage you need in a pre-approved device and  save time and effort of designing the power conversion in your system. ETA-USA desktop adapters hold UL, TUV, and UKCA 62368-1 safety certifications and meet FCC conducted and radiated emissions standards.  

Most important, ETA-USA custom DC connector program allows you to pick the DC interface of your choice. Choose from our pre-approved connector list or contact a technical representative with connector you want to use and the power requirement you need. Our staff are trained to ensure the connector will meet regulatory safety compliance and can recommend substitutes if needed. Best of all, ETA-USA has a low minimum order quantity for custom connector options (30 pcs) and customers can procure 1-2 evaluation units to test before they commit to a final design.  

See some of our  popular desktop ITE adapter models below, and contact an ETA-USA representative . All models are RoHS/REACH and DOE VI compliant.

All ETA-USA products are TAA compliant. 

Standard models can be purchased from an Authorized ETA-USA Distributor. Customized options can be ordered from an ETA-USA sales representative.

65W ITE Desktop Adapter- DTL65 Series

DTL65-SX-W6

  • Universal Input: AC 100~240V 50/60 Hz
  • IEC320-C14 AC inlet  (3 prong)
  • No load power consumption <210mW
  • Available Voltages: 5, 12, 15, 19, 24, 36, 48
  • Short circuit, OVP, OCP protection
  • Operating Temp: 0°C~60°C
  • UL/TUV/EN 62362-1 Safety, FCC 15 Class B
  • Customized cable and DC connector available

DTL65-SX-WL6

  • Universal Input: AC 100~240V 50/60 Hz
  •  3-pole IEC320-C6 and 2-pole C8 AC inlet available
  • No load power consumption <150mW
  • Meets LPS (Limited Power Source) Requirements
  • Available Voltages:  12, 15, 19, 24, 28,  48
  • Short circuit, OVP, OCP protection
  • Operating Temp: -20°C~70°C
  • UL/TUV/EN 62362-1 Safety, FCC 15 Class B
  • Customized cable and DC connector available

120W ITE Desktop Adapter- DTD120 Series

DTD120-SX-F-W6

  • Universal Input: AC 100~240V 50/60 Hz
  • IEC320-C14 AC inlet  (3 prong)
  • No load power consumption <150mW
  • Available Voltages: 12, 15, 19, 24, 28, 48
  • Short circuit, OVP, OCP protection
  • Operating Temp: -20°C~70°C
  • UL/TUV/EN 62362-1 Safety, FCC 15 Class B
  • Customized cable and DC connector available

300W ITE & Medical Desktop Adapter- DTMF300 Series

DTMF300-SX-F-W6

  • Universal Input: AC 100~240V 50/60 Hz
  • IEC320-C14 AC inlet  (3 prong) or IEC320-C18 (2 prong)
  • I/O switch optional, meets IP42 with I/O switch removed
  • 2x MOPP and BF applications
  • No load power consumption <0.5W
  • Available Voltages: 12, 15, 19, 24, 28, 48, 54
  • Short circuit, OVP, OCP protection
  • Operating Temp: -30°C~60°C
  • UL/TUV/EN 62362-1 (ITE) & 60601-1 (Medical) Safety, FCC 15 Class B
  • Customized cable and DC connector available

400W ITE & Medical Desktop Adapter- DTMF400 Series

DTMF400-SX-F-W6

  • Universal Input: AC 100~240V 50/60 Hz
  • IEC320-C14 AC inlet  (3 prong)
  • Meets IP42
  • 2x MOPP and BF applications
  • No load power consumption <0.5W
  • Available Voltages: 12, 15, 19, 24, 28, 48, 54
  • Short circuit, OVP, OCP protection
  • Operating Temp: -30°C~60°C
  • UL/TUV/EN 62362-1 (ITE) & 60601-1 (Medical) Safety, FCC 15 Class B
  • Customized cable and DC connector available

Government and Federal Agency  Customers

ETA-USA is ready to work with the US government. See our capabilities page for more information. Government P-cards accepted. 

MULTIPLE OUTPUT DESKTOP POWER SUPPLY-DTE180 SERIES

ETA-USA offers several model lines of dual and triple output AC/DC and DC/DC converters in chassis mount, PCB mount, and external desktop adapter for ITE applications. All models are and TAA compliant and available to purchase from an ETA-USA authorized distributor.

The DTE series is an external desktop style AC/DC multiple output power supply that provides 180W of rated DC power. Additional multiple output series can be found below. 

· Chassis mount AC/DC  WR series · PCB mount AC/DC  DAC series · PCB mount DC/DC multiple output O series · Desktop adapter multiple output DTE180 series ·

AC/DC Desktop Multiple Output Power Supply-DTE180 

Input: AC 90-264V 50/60Hz

              Current:  3 Arms max

              Inrush: 25A @ 115V, 50A @ 230V Max at Cold start

              Power factor: > 0.95 @115VAC; > 0.90 @230VAC @full load

Inlet: IEC320-C14

Dual Output- 0512: +5V @ 14A, +12V @ 15A

Dual Output- 1212: +12V@ 15A, -12V @ 1A

Triple Output- 03X: +5V @ 14A, +12V @ 15A, -12V @ 1A

Efficiency: >86% Typical

Operating Temp:  -20°C~60°C

Compliance : DOE VI, RoHs3, REACH, UL/EN/TUV/UKCA/IEC 62368-1, FCC Class B


DTE180 Series Customization

As with all ETA-USA desktop adapters, we offer customer specified DC connector and cable assemblies with a low minimum order. Our semi-custom page showcases DC connector options with no impact on unit costs. Customers are welcomed to specify their own connector also, contact an ETA-USA  representative for more information or to request an evaluation unit.


Government and Federal Agency  Customers

ETA-USA is ready to work with the US government. See our capabilities page for more information. Government P-cards accepted. 

MULTIPLE OUTPUT AC/DC POWER SUPPLIES-WR Series

ETA-USA offers several model lines of dual and triple output AC/DC and DC/DC converters in chassis mount, PCB mount, and external desktop adapter for ITE applications. All models are and TAA compliant and available to purchase from an ETA-USA authorized distributor.

The WR series offers a range of dual and triple output, chassis mount AC/DC power supplies from 15W to 100W of rated DC power. Additional multiple output series can be found below. 

·Chassis mount AC/DC  WR series · PCB mount AC/DC  DAC series · PCB mount DC/DC multiple output O series · Desktop adapter multiple output DTE180 series ·

AC/DC Multiple Output Power Supplies-WR Series 

Multiple Output Power Supply 30W ETA-USA

WRM SERIES: 15 Watt AC/DC Multiple Output Power Supply

Input: AC 85V~264V 50/60Hz or DC 125V~370V
              Current: 0.4 Arms Max,
              Inrush: 20A @ 110V, 40A @ 220V Max at Cold start
              Max Leakage: 0.75mA
Dual Output -Isolated Ground: 5V , 12V…. 12V, 12V….15V, 15V
Operating Temp: 0~70 °C, De-rates Linearly starting at 50°C 

WRT SERIES: 25 & 30 Watt AC/DC Multiple Output Power Supply

Input: AC 85V~264V 50/60Hz or DC 125V~370V
              Current: 0.65 Arms Max,
              Inrush: 20A @ 110V, 40A @ 220V Max at Cold start
              Max Leakage: 0.75mA
 
Dual Output-Common Ground : +/-5V, +/-12V, +/-15V
Dual Output -Isolated Ground: 5V , 12V…. 5V ,  24V 
Triple Output: 5V &  +/-12V…. 5V  & +/-24V
Operating Temp: 0~70 °C, De-rates Linearly starting at 50°C 
 

WRB SERIES: 50 Watt AC/DC Multiple Output Power Supply

Input: AC 85V~264V 50/60Hz or DC 125V~370V
              Current: 1.2 Arms Max,
              Inrush: 20A @ 110V, 40A @ 220V Max at Cold start
              Max Leakage: 0.75mA
Dual Output -Isolated Ground: 5V , 12V…. 5V ,  15V…. 5V, 24V …. 12V, 12V…. 15V, 15V
Triple Output:5V &  +/-12V…. 5V  & +/-24V
Operating Temp: 0~70 °C, De-rates Linearly starting at 50°C 

WRC SERIES: 75 Watt AC/DC Multiple Output Power Supply

Input: AC 85V~264V 50/60Hz or DC 125V~370V
              Current: 1.8 Arms Max,
              Inrush: 20A @ 110V, 40A @ 220V Max at Cold start
              Max Leakage: 0.35mA
 
Dual Output -Isolated Ground: 5V , 12V…. 5V ,  24V 
Operating Temp: 0~70 °C, De-rates Linearly starting at 50°C 
 

WRD SERIES: 100 Watt AC/DC Multiple Output Power Supply

Input: AC 85V~264V 50/60Hz or DC 125V~370V
              Current: 1.8 Arms Max,
              Inrush: 20A @ 110V, 40A @ 220V Max at Cold start
              Max Leakage: 0.35mA
 
Dual Output -Isolated Ground: 5V , 12V…. 5V ,  24V 
Operating Temp: 0~70 °C, De-rates Linearly starting at 50°C 
 
All models are RoHS compliant.
For additional information regarding the WR series or any other ETA-USA power conversion product, contact one of our technical representatives today!
ETA-USA is ready to work with the US government. See our capabilities page for more information. Government P-cards accepted.